EXPERIMENTAL STUDY ON THE CEILING RADIATION COOLING/HEATING SYSTEM USING GROUNDWATER
–PMV control on the flow rate of the groundwater drawing pump and the circulation pump–
Hiroo TARUMIYasukuni SAKAMOTORyoichi KUWAHARAMakoto NISHIZAWAKazuo IWASE
Author information
JOURNAL FREE ACCESS

2014 Volume 20 Issue 44 Pages 191-195

Details
Abstract
PMV control system was applied for a ceiling radiation cooling/heating system utilizing groundwater as heat source/sink. System improvements including extension of the ceiling radiation panel and inverter control of pumps were carried out in the 2012. The research results in summertime cases are summarized below:
1) Indoor PMV values were settled in the range of 0.2-0.6 which was narrower than the previous year. 2) The power consumption of the pumps dropped to 1/3 of the previous year, and that of the whole system containing an makeup air unit dropped to 2/3.