STUDY ON MAGNETIC SHIELDING EFFECT AROUND THE ELECTRIC POWER LINE IN VARIOUS MATERIALS OPENING CONDITIONS
Naoya KUBOKazunori NISHIMURANobuyoshi KIYOTA
Author information
JOURNAL FREE ACCESS

2017 Volume 23 Issue 54 Pages 531-534

Details
Abstract

In magnetic shielding with the opening of the magnetic material around the electric power line, I confirmed the difference of effect in various opening conditions by an experiment.
The results are as follows. The shielding effect was low under conditions of opening rate more than 30%. The difference by opening pattern was small, but the effect with the staggered pattern was high in a specific condition. By the method to increase area of each opening, the effect decreased in the neighborhood of the power line, but there was not the difference in the distant place.