AIJ Journal of Technology and Design
Online ISSN : 1881-8188
Print ISSN : 1341-9463
ISSN-L : 1341-9463
Environmental Engineering
A FIELD MEASUREMENT ON LOW TEMPERATURE HEATING AND HEATING PERFORMANCE IMPROVEMENT BY MEANS OF CONVECTION ENHANCEMENT IN RADIANT HEATING WITH PLASTIC MULTI-TUBULAR RADIATORS IN A RESIDENTIAL BUILDING
Yuhei FUKADAItaru TAKAHASHI
Author information
JOURNAL FREE ACCESS

2022 Volume 28 Issue 69 Pages 739-744

Details
Abstract

This paper describes results of a field measurement in which the feasibility of low temperature heating and heating performance improvement by means of convection enhancement around radiators were examined in radiant heating with plastic multi-tubular radiators in an existing reinforced concrete house without thermal insulation. Radiant heating with plastic multi-tubular radiators can make both room air temperatures and MRTs 22〜25℃ and PMVs 0 〜± 0.5 with supply temperature being 30〜36℃. Convection enhancement around radiators by means of small DC fans increases their thermal emissions in 140W/m2 at most.

Content from these authors
© 2022, Architectural Institute of Japan
Previous article Next article
feedback