Closed-Form Equations for Room Smoke Filling During an Initial Fire
Ken MatsuyamaYutaka MisawaTakao WakamatsuKazunori Harada
著者情報
ジャーナル フリー

1999 年 19 巻 1 号 p. 27-38

詳細
抄録
Closed-form equations were derived to calculate the smoke layer height and temperature in the room of fire origin. First of all, a conventional zone type model was introduced and verified against the full-scale experimental data. Then, by using the calculation model, virtual experimental data were created varying the building design parameters such as fire growth rate, floor area and ceiling height. Regression equation was derived for smoke layer temperature using the virtual experimental data that correlates the dependence on building design parameters. As to the smoke layer height, an analytical formula (Tanaka's formula) was verified against virtual experimental data. This type of simple, hand-calculable formula would be useful for practitioners in fire safety engineering design of building for evacuation safety from smoke.
著者関連情報
© 1999 Center for Fire Science and Technology, Research Institute for Science and Technology, Tokyo University of Science