電気学会論文誌D(産業応用部門誌)
Online ISSN : 1348-8163
Print ISSN : 0913-6339
ISSN-L : 0913-6339
論文
瞬時無効電力補償装置を並列接続した三相系統連系インバータ
高木 一斗藤田 英明
著者情報
ジャーナル フリー

2018 年 138 巻 6 号 p. 530-537

詳細
抄録

This paper introduces a new three-phase grid-connected inverter for commercial-scale 10-50-kW photovoltaic systems installed on underutilized assets such as rooftops of office buildings. The circuit topology combines an inductorless active bridge with a parallel-connected PWM inverter behaving as an instantaneous reactive power compensator. The active bridge, referred to as 120°-conduction inverter, performs a fundamental-frequency switching and outputs a 120°-block-shaped current, while the instantaneous reactive power compensator suppresses the harmonic current included in the block-shaped current. The main advantage of this strategy is the size reduction of the required ac inductor by a factor of four as well as the reduction in switching device power losses. The theoretical analysis clearly shows that the compensator controls only instantaneous reactive power to synthesize a sinusoidal current, thus eliminating the need for an electrolytic capacitor. A 5-kW experimental setup validates the operating principle and control method of the proposed inverter, and exhibits an inverter efficiency as high as 98.8%.

著者関連情報
© 2018 電気学会