2024 年 144 巻 8 号 p. 629-630
This study proposes a partial PAM inverter with power decoupling operation in discontinuous current mode for UPS. Simulation results indicate that THD of 0.27% was achieved in the inverter output voltage. Moreover, the second-order harmonic of the input power ripple reduced by 98.5% compared to the DC components.