電気学会論文誌D(産業応用部門誌)
Online ISSN : 1348-8163
Print ISSN : 0913-6339
ISSN-L : 0913-6339
三相システムの非正弦波不平衡状態における各相別無効電流補償法-準瞬時無効電力補償装置-
田中 俊彦舩曳 繁之難波 江章
著者情報
ジャーナル フリー

2001 年 121 巻 3 号 p. 383-390

詳細
抄録

Many researchers have attempted to clarify the definitions of active power, reactive power, active current, reactive current, etc. for unbalanced and non-sinusoidal three-phase situations. The so-called pq theory has given a new definition of instantaneous reactive power, and it has been discussed and developed by many authors. In this paper, the merits and demerits of the instantaneous reactive power compensator are discussed. It is shown theoretically that applying instantaneous reactive power compensation to unbalanced three-phase systems has a serious disadvantage in that it causes third-order harmonic currents on the source side, which problem cannot be avoided. To overcome this problem the authors propose a new approach, and name it the “quasi-instantaneous” reactive power compensator. It compensates individual-phase reactive currents. The basic principles of the quasi-instantaneous reactive current compensator are discussed in detail, and its validity is confirmed using digital simulation. In particular the authors show that the power factor of each phase becomes unity on the source side, but the source currents remain unbalanced when the proposed method is applied.