抄録
This paper discusses automatic gain adjustment in a fully-digital-controlled shunt active filter intended for installation on power distribution systems. This is the first step in cooperative control of multiple shunt active filters based on voltage detection for harmonic damping throughout power distribution systems. In general, an optimal control gain is equal to the characteristic impedance of a distribution line. However, it is difficult to know circuit parameters of a real distribution line, which depend strongly on feeder connections, shunt capacitors and loads. Therefore, the main purpose of the gain adjustment is to help the active filter to damp out harmonic propagation without considering the circuit parameters. Moreover, the gain adjustment can reduce the compensating current and losses in the active filter. The active filter having the function of automatic gain adjustment is experimentally compared to that with a constant gain. Experiment results verify the effectiveness of the active filter having the function of automatic gain adjustment.