直列形アクティブフィルタの整合変圧器に生じる直流偏磁とその抑制法
長谷川 博司Sunt Srianthumrong赤木 泰文藤田 英明
著者情報
ジャーナル フリー

2002 年 122 巻 7 号 p. 744-751

詳細
抄録
This paper deals with a series active filter for harmonic-current compensation of a large-capacity diode rectifier with a capacitive load. Flux satulation may occur in a series matching transformer for connecting the series active filter to the ac side of the diode rectifier. This paper develops an analog controller of a dc magnetizing current flowing in the matching transformer, along with a model for the controller, to avoid the flux satulation. Operating characteristics of the controller are theoretically and exprimentally discussed, taking into account both an offset voltage in the controller and an error in a current sensor. Finally, this paper discusses a relation between magnetizing characteristics of the matching transformer and the amplitude of the magnetizing current.