IEEJ Transactions on Power and Energy
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
Special Issue Paper
Influence of Field Mutual Leakage Reactance in Generator Model on Dynamic Behavior
—Study on Sudden Short Circuit, Load Rejection and PSS Eect—
Daisuke HiramatsuKaoru KoyanagiKaiichirou HirayamaYoichi UemuraTadashi TokumasuMikio TakabatakeToshiyuki Satoh
Author information
JOURNAL FREE ACCESS

2003 Volume 123 Issue 12 Pages 1495-1503

Details
Abstract
This paper describes the effect of mutual leakage reactance in rotor circuit (Canay reactance) on analysis of generator transient and dynamic behavior. The authors derived a detailed equivalent circuit model for 48P-15.75MVA generator, and analyzed sudden short circuit and load rejection phenomena of the generator by simulations using the electromagnetic transients program (ATP-EMTP), and compared the results with the experimental data. In addition to these analyses, the influence of mutual leakage reactance on analysis of power system dynamic stability was investigated.
Content from these authors
© 2003 by the Institute of Electrical Engineers of Japan