IEEJ Transactions on Power and Energy
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
Paper
A Study on Capacitive Current Switching Capability by Flashover Characteristics between Contacts of Circuit Breakers
Mitsuru ToyodaHirokuni AoyagiHitoshi Mizoguchi
Author information
JOURNAL FREE ACCESS

2003 Volume 123 Issue 2 Pages 230-236

Details
Abstract
This paper describes the capacitive current interruption capability of circuit breakers from the view point of flashover characteristics between contacts of breakers. Authors obtained flashover characteristics between contacts of breakers with short distance by comparing with new condition and eroded condition after 3 shots of T60 according to new JEC 2300 (1998) and new IEC 62271-100. By comparison of flashover characteristics and electric field calculation obtained by the measurement of new and eroded contacts, deterioration of the dielectric capability is of 10 to 20 %. Authors also conducted flashover tests for the contacts and nozzle after significant number of interruption. The total amount of interruption can be considered as the maximum possible interruption according to CIGRE research. The deterioration of dielectric capability is of 10 to 30 %.
Content from these authors
© 2003 by the Institute of Electrical Engineers of Japan
Previous article Next article
feedback
Top