IEEJ Transactions on Power and Energy
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
Paper
Development of a 66kV Class Rectifier Type Fault Current Limiter System
Takeshi OhkumaYoshibumi SatoYoshihisa TakahashiNoriaki TokudaMasaki MuraiNorihisa NagasakiKyousuke Yuguchi
Author information
JOURNAL FREE ACCESS

2003 Volume 123 Issue 7 Pages 838-843

Details
Abstract
A fault current limiter (FCL) is extensively expected to suppress fault current, particularly required for trunk power systems heavily connected high-voltage transmission lines, such as 500 kV class power system which constitutes the nucleus of the electric power system. By installing such FCL in the power system, the system interconnection is possible without the need to raise the capacity of the circuit breakers, and it is expected that FCLs may be used in more efficient power system design. For these reasons, FCLs based on various principles of operation have been developed in the world.
In this paper, we have proposed a new type of FCL system, consisting of solid-state diodes, DC coil and bypass AC coil, and described the specification of distribution power system and 66 kV class FCL model. Also we have proposed a 66 kV class prototype single-phase model and the current limiting performance of this model was evaluated using a short circuit generator.
Content from these authors
© 2003 by the Institute of Electrical Engineers of Japan
Previous article Next article
feedback
Top