IEEJ Transactions on Power and Energy
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
Paper
Diagnosis for Water-Tree Deteriorated Cross-Linked Polyethylene Cable by the Improved Residual-Charge Measurement
Kazuhisa MiyajimaHiroyuki KonKazuo WatanabeKatsumi Uchida
Author information
JOURNAL FREE ACCESS

2005 Volume 125 Issue 2 Pages 199-205

Details
Abstract
We have been investigating the residual-charge measurement as a diagnostic method for water-tree deteriorated cross-linked polyethylene cable. In the method that we proposed here, the residual charge component detected by higher AC voltage application could correspond to longer water trees. Therefore, this method is effective to diagnose the degree of water-tree deterioration in the long distance cable line.
Content from these authors
© 2005 by the Institute of Electrical Engineers of Japan
Previous article Next article
feedback