IEEJ Transactions on Power and Energy
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
Paper
Study on Terminal Voltage and Power Factor Control of Induction Generators for Wind Power Generation System
Tomonobu SenjyuNorihide SueyoshiRyo KuninakaKatsumi UezatoHideki FujitaToshihisa Funabashi
Author information
JOURNAL FREE ACCESS

2005 Volume 125 Issue 3 Pages 286-292

Details
Abstract

This paper deals with two types of control method concerning induction generator used in wind power generating station. One is aiming at keeping the voltage magnitude of the node of the station and the other is aiming at keeping the constant power factor through the branch connecting to the station. Both of them are able to be in controllable area by adjusting generator reactive power using compensating capacitor. At first, the theoretical equations expressing terminal voltage and power factor for induction generator are derived, and then the compensating capacitor corresponding to the wind velocity variation is determined quantitatively. By using the proposed control method, it is confirmed to be able to keep the terminal voltage and operating power factor of wind power generation system to a target value even in the case when the abrupt deviation is caused by wind power disturbance.

Content from these authors
© 2005 by the Institute of Electrical Engineers of Japan
Previous article Next article
feedback