2007 Volume 127 Issue 12 Pages 1299-1305
The power frequency withstand voltage tests are specified on electric power equipment in JEC-0102 by evaluating the lifetime reliability with a Weibull distribution function. It may be applied on 66-154kV transformer for non-effectively grounded voltage class. The present paper describes the results that measured AC insulation characteristics (Voltage-time characteristics) and Weibull parameters for oil-filled transformer of 66-154kV class. These measurement parameters were compared with the conventional Weibull parameters, which were applied for oil-filled transformer of voltage class above 154kV. Furthermore the non-partial discharge test voltage was evaluated by trial calculations, using the parameters obtained this time or typical parameters.
The transactions of the Institute of Electrical Engineers of Japan.B
The Journal of the Institute of Electrical Engineers of Japan