IEEJ Transactions on Power and Energy
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
Paper
Evaluation of Amorphous Transformer by Optimum Capacity Selection based on the Load Curve Pattern of Customers
Masaaki TakagiHiromi YamamotoKenji Yamaji
Author information
JOURNAL FREE ACCESS

2009 Volume 129 Issue 1 Pages 205-214

Details
Abstract
Energy loss in transformer is composed of no-load loss and load loss. No-load loss of amorphous transformer (i.e. amorphous metal-based transformer) is less by about 70% compared with traditional transformers (e.g. silicon steel-based transformer). However, amorphous transformers have disadvantages of high cost and high load loss parameter compared with traditional transformers. Furthermore, there are varieties of transformer capacities, and the customers who would buy new transformer have many choices.
In this paper, the authors propose an algorithm for optimum transformer selection based on the load curve patterns of customers. It is possible to select the capacity that minimizes the total cost by measuring equivalent load Qe that is the root mean square of load. It becomes clear that amorphous transformer is effective in achieving substantial energy saving compared with traditional transformer.
Content from these authors
© 2009 by the Institute of Electrical Engineers of Japan