Synchronized Injection Method of Distributed Inter-Harmonic Currents and its Application to Detection of Islanding Operation under Clustering Installation of Distributed Generators
Shoji NishimuraYoshihiro HadaMasahiro OruiFumio YamamotoHiromu KobayashiToshiro Matsumura
Author information
JOURNAL FREE ACCESS

2009 Volume 129 Issue 11 Pages 1373-1382

Details
Abstract
This paper describes synchronized injection method of distributed inter-harmonic currents, and inspection of new islanding operation detection method for clustering installation as its application. If small distributed generators (DG) interconnected with low voltage system are installed under clustering, when a intersystem fault occur between high and low voltage grid, islanding phenomena will pose a problem. The following methods are conventionally considered as a measure.
(1) Method by distribution system facilities
(2) Application of conventional islanding detection method (indirect detection of earth fault)
However, the subject of maintenance of a system occurs by (1). The subject to which detection time becomes long depending on system conditions can be considered by (2). Then, in order to solve these subjects, we developed this new method.