Special Issue Paper
Mechanism of Occurring Over-Voltage Phenomena in Distributed Power System on Energization of Transformers
Yoshiki NakachiFukashi UedaTakuya KajikawaTooru AmauHirokazu KameyamaHisanori Ito
Author information
JOURNAL FREE ACCESS

2010 Volume 130 Issue 1 Pages 25-34

Details
Abstract
This paper verifies the mechanism of occurring over voltage phenomena in the distributed power system on energizing the transformer. This over-voltage, which is observed at the actual distributed power system, with heavy inrush current is found to occur at about 0.1-0.2sec after the energizing and continue for a duration of more than 0.1[sec]. There is a concern that this over-voltage may operate the protection relay and deteriorate the insulation of apparatus. It is basically caused by the resonance between the shunt capacitors and saturated/unsaturated magnetizing inductance of transformer, system inductance. By using analytical formulation of a simple equivalent circuit, its mechanism has been verified through simulations carried out by using EMTP. Moreover, the sympathetic interaction between transformers is prolonged the duration of the over-voltage by the field test data is discussed in this paper.