IEEJ Transactions on Power and Energy
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
Paper
Affect of Voltage Sags on Electro-magnetic Contactor
—A New Parameter for Sag Characteristics—
Isao IyodaYoshitaro AndoSompathana PounyakhetMasaya HirataToshifumi Ise
Author information
JOURNAL FREE ACCESS

2010 Volume 130 Issue 5 Pages 510-516

Details
Abstract

Sensitivity of electro-magnetic contactors for voltage sags is studied by experiments and simulations. An experimental circuit with a semiconductor fault switch that controls the phase angle of system voltage at the initial point of voltage sags is developed. The phase angle is a new parameter for voltage sags. The operating characteristics of the contactor are evaluated in various conditions. It is found that shallow sags may cause faster trips of contactors compared to deep sags in some cases. The reason of this phenomenon is analyzed with simulations.

Content from these authors
© 2010 by the Institute of Electrical Engineers of Japan
Previous article Next article
feedback
Top