IEEJ Transactions on Power and Energy
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
Paper
Restraint Method of Voltage Total Harmonic Distortion in Distribution Network by Power Conditioner Systems using Measured Data from IT Switches
Shoji KawasakiKazuki ShimodaMotohiro TanakaHisao TaokaJunya MatsukiYasuhiro Hayashi
Author information
JOURNAL FREE ACCESS

2011 Volume 131 Issue 12 Pages 936-944

Details
Abstract
Recently, the amount of distributed generation (DG) such as photovoltaic system and wind power generator system installed in a distribution system has been increasing because of reduction of the effects on the environment. However, the harmonic troubles in the distribution system are apprehended in the background of the increase of connection of DGs through the inverters and the spread of power electronics equipment. In this paper, the authors propose a restraint method of voltage total harmonic distortion (THD) in a whole distribution network by active filter (AF) operation of plural power conditioner systems (PCS). Moreover, the authors propose a determination method of the optimal gain of AF operation so as to minimize the maximum value of voltage THD in the distribution network by the real-time feedback control with measured data from the information technology (IT) switches. In order to verify the validity of the proposed method, the numerical calculations are carried out by using an analytical model of distribution network interconnected DGs with PCS.