2012 Volume 132 Issue 4 Pages 341-349
The capacity of Distributed Generators (DGs) connected to grid by inverters are growing year and year. The inverters are generally controlled by PLL (Phase Locked Loop) in order to synchronize with power system frequency. Power systems will become unstable, if the capacity of inverter type DGs become larger and larger, because inverter frequency is controlled just to follow the frequency decided by other synchronous generators. There is the idea that inverters are controlled to behave like a synchronous generator. This concept is called Virtual Synchronous Generator (VSG). In this paper, a control scheme of VSG is presented, and the design method of required energy storage and the ability of grid stabilizing control by VSG is investigated by computer simulations.
The transactions of the Institute of Electrical Engineers of Japan.B
The Journal of the Institute of Electrical Engineers of Japan