Effective Installation Strategies of Fault Current Interrupting Arcing Horns Considering Operational Coordination with Responses of Line Protection Relays
Toshiya OhtakaHideyuki Kameda
Author information
JOURNAL FREE ACCESS

2015 Volume 135 Issue 6 Pages 372-379

Details
Abstract

The Fault Current Interrupting Arcing Horns (FCIAH) is a new type of arcing horns, which operates to break fault current within one cycle of alternating current and contributes to reducing the instantaneous power interruption due to the opening of a circuit breaker. However, reportedly the transmission line is often tripped by the line protection relay in some power utilities, even though the FCIAH successfully could break fault current. In this paper, we have investigated primary factors in the unwanted operation of the line protection relays at the current interruption by the FCIAH, and have proposed effective installation strategies of the FCIAH considering the operational coordination with the responses of the line protection relays.