IEEJ Transactions on Power and Energy
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
Paper
Prediction Model on Room Temperature Side-Effect due to FastADR Aggregation for a Cluster of Building Air-Conditioning Facilities
Taku NaramuraJunji MorikawaChuzo Ninagawa
Author information
JOURNAL FREE ACCESS

2016 Volume 136 Issue 4 Pages 432-438

Details
Abstract
In this paper, we have constructed an Auto Regressive(AR) and Neural Network (NN) combined type prediction model for responsive change in the room temperature trend due to the Fast Automated Demand Response (FastADR) power limitation of office building air-conditioning facilities. We defined the average of differences between room temperature and setpoint of each indoor unit for the entire building as a FastADR side-effect index for the building. Prediction experiments using an actual office building showed that the root mean square prediction error of our model was 0.23 degrees Celsius for 5 minutes after the FastADR. This prediction ability is considered sufficient to estimate the side-effect of FastADR power limitation.
Content from these authors
© 2016 by the Institute of Electrical Engineers of Japan
Previous article Next article
feedback