IEEJ Transactions on Power and Energy
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
Paper
Study of Transformer Winding Resonance Phenomenon by Lightning Surges at Substations
Toshiaki Ueda
Author information
JOURNAL RESTRICTED ACCESS

2021 Volume 141 Issue 2 Pages 181-187

Details
Abstract

In recent year, there is the example that oscillating overvoltage occurs by the lightning strike to transmission line, and the transformer in substation breaks down. Lightning surges at two 77kV substations have been measured from 1990 to 1993. In this paper, I analyze the lightning surge waveform measured at substation including the transformer winding and show the relationship between the voltage of transformer neutral point and vibration frequencies of surges. Then, I show an outbreak condition of the qualitative resonance-related overvoltage by a frequency and the waveform pattern using XTAP (eXpandable Transients Analysis Program) and show the result that I inspected about a suppression effect of the transformer neutral point voltage with transmission line arrester and neutral arrester.

Content from these authors
© 2021 by the Institute of Electrical Engineers of Japan
Previous article Next article
feedback
Top