IEEJ Transactions on Power and Energy
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
Paper
A SVR Control Method with Switching Multiple LDC Parameters Using Measurement Data of Distribution Systems
Ryuta GotoTakao TsujiTsutomu OyamaNaoki HayashiKazuki TakahashiSatoru AkagiKazuyoshi HashikawaHideyasu HokazonoYukiyasu Kuwashita
Author information
JOURNAL RESTRICTED ACCESS

2021 Volume 141 Issue 5 Pages 374-383

Details
Abstract

The voltage regulation in distribution systems becomes more important these days due to the more complicated power flow profile caused by the integration of variable renewable energy sources such as photovoltaic (PV). Step voltage regulator (SVR) and load ratio controlled transformer (LRT) have been mainly used for the voltage regulation conventionally based on decentralized control methods using line drop compensation (LDC) logic for estimation of voltage drop at secondary side of the SVR. Here, it has been required for distribution system operator to determine LDC parameters properly to estimate the voltage drop based on locally measured information. Hence, in this paper, we proposed an advanced LDC logic in which the parameters can be flexibly switched based on the power flow conditions. The effectiveness of the proposed method was verified using 41-node distribution system model with PV.

Content from these authors
© 2021 by the Institute of Electrical Engineers of Japan
Previous article Next article
feedback