2023 Volume 143 Issue 10 Pages 559-566
Aged CVTs have been often used in substations, but the expected lifetime of CVTs is unclear, so that it is difficult to determine the appropriate renewal time. Therefore, in this paper, we focus on oil-impregnated paper capacitors inside CVTs and propose a concept to evaluate their expected lifetime based on the partial discharge (PD) progress characteristics. By using a fundamental oil-impregnated paper capacitor model, the PD progress characteristics were measured and discussed from electrical and optical aspects.
The transactions of the Institute of Electrical Engineers of Japan.B
The Journal of the Institute of Electrical Engineers of Japan