Initial Current Displacement in Transmission Line Caused by Faults in Power System
Muneyuki UdoKaoru Koyanagi
著者情報
ジャーナル フリー

1986 年 106 巻 3 号 p. 295-301

詳細
抄録
This paper relates to the magnitude of the DC transient component and that of the AC fundamental component contained in line current caused by power system faults. The condition that the former could exceed the latter can be expressed graphically by the region inside the circles on the plane with P-Q coordinates where P-Q corresponds to power flow in the line before fault occurrence. The circles for various faults in power systems with singlle-circuit and double-circuit transmission lines are shown.
著者関連情報
© The Institute of Electrical Engineers of Japan