1993 Volume 113 Issue 9 Pages 1003-1011
This paper investigates the voltage stability in a single OLTC (On-load Tap Changer) system, which consists of a single OLTC and multiple generators as well as loads. It is shown that the sensitibity of load voltage to tap position, dV/dn=(I1=exact value), plays an important roll, independent of the existense of the equilibrium of the tap position. That is, when the equilibrium exists, the region where I1>0 is in the stabity region; if the equilibrium disappears, the stability region aslo disappears but the voltage is still recovering in the region where the I1>0. Based on these results, the region of reverse control action of OLTC is defined as the region where I1<0. It is proved that another sensitibity, I2, which is defined as dV/dn when constant power characteristics are assumed for loads, can be used to estimate the region of reverse control action when the exact load charecteristics are not available.
The transactions of the Institute of Electrical Engineers of Japan.B
The Journal of the Institute of Electrical Engineers of Japan