IEEJ Transactions on Power and Energy
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
Protective Systems and its Protective Switching Elements on Local Failures of Large Slow-Capacitor Bank System
Mitsuo HasegawaKunikazu InoueIsao Ueno
Author information
JOURNAL FREE ACCESS

1994 Volume 114 Issue 10 Pages 994-1001

Details
Abstract
In various applications of pulsed power technologies, large capacitor bank systems are used to feed high current impulse to different experimental devices. The accidental electric breakdown in one of the capacitors in a parallel connection of the large bank may result in serious damages such as mechanical explosion and oil effusion or fire. In most fast banks, each unit capacitor has an output gap switch, which is expected to decouple the capacitors one another. However, no such special element is adopted usually in the slow bank system, partly because of the economical consideration.
We have developed a novel and inexpensive protective element for these relatively slow capacitor banks, utilizing a concept of the enclosed type of the fast breakers. The principle of the operation of the protection elements is verified by a simulation experiment. Their practical effectiveness is also successfully demonstrated in the application to the system of the pulsed high magnetic field generator.
Content from these authors
© The Institute of Electrical Engineers of Japan
Previous article Next article
feedback
Top