Abstract
A new Transient Stability Controller system (TSC) based on on-line transient stability calculation has been developed. The TSC system prevents the power system from wide-area blackout by shedding generators optimally when a serious fault occurs. This system consists of a central processing unit(TSC-P), and four local units for fault detection(TSC-C), and seventeen units for generator shedding(TSC-T). The TSC-P selects optimal generators to be shed for stabilization based on on-line transient stability calculation for contingencies at 500kV lines and buses every five minutes. The results are transmitted to the TSC-Cs periodically. Should any fault occur, only one TSC-C will detect the fault occurrence and send control signals to the TSC-Ts which actually generate shedding signals. To realize the TSC system, essential are fast stability evaluation method for a large number of contingencies and effective selection method of optimal generators to be shed for stabilization.
This paper presents total algorithms applied in the TSC-P, the results of algorithm verification tests using a prototype system combined with a large-scale analog simulator, and the characteristics of the actual system.