Medium-Size Distribution Transformer Diagnostics
Yoshiki SusakiOsamu NakamuraFumio KawachiMasayoshi YamaokaTakeshi NishimuraTadashi Kuriyama
Author information
Keywords: CO, CO2
JOURNAL FREE ACCESS

1995 Volume 115 Issue 10 Pages 1154-1161

Details
Abstract
An improved method of degradation diagnosis for medium-size distribution transformers is described. The proposed method uses refined criteria of degradation for specific application for 200-to 1000-kVA range transformer diagnostics. The new criteria were established with a 95% confidence limit of data after extensive case studies focusing on the relationship between the amounts of CO and CO2 generated in transformer oil and the length of operating time of transformer. Another feature of this diagnostic technique is the provision of a capability to estimate the thermal history of the insulation material by examining the amounts of certain trace products of decomposition present in the transformer oil. For this purpose, a thermal history discriminant chart was devised by application of a canonical discriminant analysis method.