Abstract
The authors propose a new power control method which is suitable for the MHD power generation system which consists of nonequilibrium disk generator and line-commutated inverter. The thermal input of generator is controlled by changing the inlet stagnation pressure, whereas the seed mass flow rate instead of the inlet stagnation pressure is utilized as a manipulated variable of power control system. It is possible that the proposed method ran realize both high performance for part load operation and fast output power control of which time constant is much shorter than the response time of thermal input. Numerical simulations are carried out for the MHD power generation system connected to infinite bus and then it is confirmed that the system is stable and shows excellent power control performance.