1996 Volume 116 Issue 10 Pages 1178-1183
This paper deals with the partial discharge inception voltage (PDIV) and breakdown voltage (BDV) characteristics of turn-to-turn insulation models for SF6 gas-insulated transformers under steep front short pulse voltages, of which waveforms are 35/65 ns and 50/370 ns. It was found out that PDIV under nano-second pulses were 1.05_??_1.15 times higher than those under standard impulse voltages and BDV under nano-second pulses were about 1.4 times higher than those under standard impulse voltages. The ratio of impulse PDIV to ac PDIV is 1.40_??_1.48 for standard impulse voltages and 1.32_??_1.37 for switching impulses.
The transactions of the Institute of Electrical Engineers of Japan.B
The Journal of the Institute of Electrical Engineers of Japan