Experimental Verification of the Effect of a Voltage-Detection-Based Shunt Active Filter for Harmonic Damping throughout a Power Distribution Line
Keiji WadaHideaki FujitaHirofumi AkagiNoboru Shibamaru
Author information
JOURNAL FREE ACCESS

1999 Volume 119 Issue 2 Pages 204-211

Details
Abstract
This paper is focused on a voltage-detection-based shunt active filter for installation on a power distribution system. A main objective of the active filter is to achieve damping of harmonic propagation coming from series/parallel resonance between capacitors for power factor correction and line inductors in the distribution system. The active filter installed at the end terminal of a distribution feeder is controlled in such a way as to present infinite impedance to the external circuit for the fundamental frequency, and as to exhibit low resistance for harmonic frequencies. As a result, the active filter acts as a damping resistor for the harmonic propagation, just like a 50-Ω terminator installed at the end of a signal transmission line. It is verified by experiment that the active filter intended for harmonic termination has the capability of harmonic damping throughout the distribution feeder.