2000 Volume 120 Issue 11 Pages 1382-1389
Authors have developed a new life estimation method for water treed 22-77 kV XLPE cables based on a very low frequency (VLF) voltage withstand test. Breakdown tests under ac and VLF were carried out, using model cables and service aged XLPE cables. Based on the breakdown tests, we calculated optimal test voltage for remaining life estimation. Recently, we had on-site testing.