Experimental Verification of Dispersed Installation of Shunt Active Filters Based on Voltage Detection for Harmonic Damping throughout Power Distribution Systems
Keiji WadaShinichi InabeHideaki FujitaHirofumi AkagiNoboru Shibamaru
Author information
JOURNAL FREE ACCESS

2000 Volume 120 Issue 8-9 Pages 1045-1053

Details
Abstract

This paper deals with dispersed installation of voltage-etection based shunt active filters for harmonic damping throughout a power distribution system. A main objective of the active filters is to achieve damping of harmonic propagation coming from series/parallel resonance between capacitors for power factor correction and line inductors in the distribution system. Either a harmonic current source or a harmonic voltage source is connected to a distribution system simulator consisting of two distribution feeders, each of which is rated at 200 V and 20 kW. A couple of active filters are installed to the simulator. As a result, it is clarified by experiment that dispersed installation on the end bus of each feeder is effective in attenuating the harmonic propagation.