IEEJ Transactions on Power and Energy
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
Fault Location for Series Compensated Parallel Lines
Tomochika MaekawaNoriyuki HashimotoMitsuru YamauraYasuhiro KurosawaHideyuki TakaniThmonori Nishida
Author information
JOURNAL FREE ACCESS

2002 Volume 122 Issue 12 Pages 1311-1320

Details
Abstract
This paper describes an error analysis and performance assessment for one-terminal and two-terminal fault locations utilizing impedance measurement techniques for series compensated parallel lines. The one-terminal fault location method is considerably influenced by the series capacitors in series compensated parallel lines. Two major factors which influence one-terminal fault location have come to light. One is the voltage and current components of lower harmonics which are close to the fundamental frequency and are generated when faults occur in series compensated parallel lines. The other is the phase angle difference of the fault current between the fault point and the fault locating point. These factors increase the locating error considerably. The transient solution of the linear circuit equation of the series compensated parallel lines is obtained and it shows that the result coincides with the simulation based on the EMTP model for series compensated parallel lines. Furthermore, two-terminal fault location using the data from both terminals is assessed. A location method using positive-sequence components is simulated with an EMTP model for the lines and shows good location accuracy.
Content from these authors
© The Institute of Electrical Engineers of Japan
Previous article Next article
feedback
Top