Simplified Prediction Method of Stack-Induced Pressure Distribution in High-rise Residential Buildings
Jae-Hun JoHo-Tae SeokMyoung-Souk YeoKwang-Woo Kim
著者情報
ジャーナル フリー

2009 年 8 巻 1 号 p. 283-290

詳細
抄録
This paper presents a simple prediction strategy for estimating the pressure distribution in high-rise residential buildings, using key parameters that affect the magnitude and distribution of stack pressure. The strategy is composed of two procedures: first, the stack pressure is predicted from parameters such as the height of the elevator shaft, the location of the neutral pressure level for each shaft, and the interior temperature of each shaft. Then, the pressure distribution of each floor is calculated using the equivalent leakage areas of the exterior and interior walls, by which finally the pressure difference across the exterior walls can be estimated. To verify the feasibility of this strategy, the predicted pressure differences across exterior walls were compared to measured data of a high-rise residential building with multiple elevator zoning. The results show that this strategy can predict pressure distribution quickly with satisfactory results for both the architectural designer and HVAC engineer.
著者関連情報

この記事は最新の被引用情報を取得できません。

© 2009 Architectural Institute of Japan
前の記事 次の記事