2023 Volume 72 Issue 1 Pages 22-30
The main foundation structure of photovoltaic power generation facilities is a steel pile foundation. Soil corrosion rate is regarded as 0.02 mm/year regardless of the soil. However, it is considered that corrosion rates of each soil are difference. In this study, we estimated the soil corrosion environment by measuring the physical properties of soil and evaluated the charge transfer resistance of each soil environment by AC impedance method that regarded soil as electrolyte, in order to investigate the effect of soil particle size on soil corrosion.
Glass beads of uniform sphere haven’t been packed close-packed structure, and porosity of soil with particle size distribution was nearly equal to regardless of particle size. But in case of the soil that included particles less than 50μm in a large quantity, porosity of the soil was increase. Porosity of soil that had similar particle size distribution was nearly equal regardless of water content. Therefore, it is suggested that the change of soil water content was replacement liquid phase and gas phase. The charge transfer resistance of soil corrosion decreased with decrease of gas phase ratio in soil. Therefore, it is suggested that the charge transfer resistance of soil corrosion might be estimated from the soil particle size distribution and water content.