Journal of the Fuel Society of Japan
Online ISSN : 2185-226X
Print ISSN : 0369-3775
ISSN-L : 0369-3775
Test on lining material to duct and stack in oil-fired power station .
Tokiharu Okubo
Author information
JOURNAL FREE ACCESS

1966 Volume 45 Issue 6 Pages 414-421

Details
Abstract
After a research on lining materials in order to prevent low-temperature corrosion occuring while fuel is being burned in a boiler, Organic lining F50S and PbHomogen are now being practised at some power plants. Performance data on the field test of these lining materials and the results of laboratory test of other resins, acid-proof bricks and castable etc. are as follows.
1. On the field test, F50S lining has proved to be remarkably effective against corrosion for about two years, and Pb-Homogen has scarcely been eroded.
2. F50S lining and Pb-Homogen have shown their superior anti-corrosion for a long period at the laboratory test, too, and also acid-proof bricks lining has effective for anti corrosion. Therefore, we need to make further studies.
3. As to other resins and castable etc., no particular anti-corrosion effect has been found.
Content from these authors
© The Japan Institute of Energy
Previous article Next article
feedback