単列管群を通過する気液二相流の流動・伝熱特性
(不等間隔配列の影響・効果)
社河内 敏彦清水 拓也辻本 公一安藤 俊剛
著者情報
ジャーナル フリー

2010 年 23 巻 5 号 p. 555-561

詳細
抄録

The tube bundle of heat exchanger is arranged with an equal space pitch arrangement generally, but using a tube bundle with unequal space pitch one the flow pattern changes and the flow resistance and heat transfer performance may be reduced and improved, respectively. In this study, as a first step the flow resistance of a single raw tube bundle with an unequal spacing is examined experimentally. The equal spacing is the tube pitch of p/d=1.5 (d: tube diameter, =15.0mm), and a unequal spacing is formed by moving only the odd' s number tube.
The experiment showed that using an unequal space pitch the flow resistance was reduced and the heat transfer performance was improved under some conditions. For example, for Reynolds number Re=Ud/ν=5×103 (U: mean superficial water velocity of coming to tube bundle), p/d=1.33, volumetric flow rate ratio of air to mixture α=0% (single-phase water flow), 10% (air-water two-phase bubbly flow), the flow resistance of the single raw tube bundle with p/d=1.33 decreases about 35, 9%, respectively, and for α=5% the heat transfer performance Num is improved about 10.5%.