気象集誌. 第2輯
Online ISSN : 2186-9057
Print ISSN : 0026-1165
ISSN-L : 0026-1165
相當温位の分布と熱雷の發生
荻原 〓二中島 武彦
著者情報
ジャーナル フリー

1940 年 18 巻 5 号 p. 166-168

詳細
抄録

A set of charts representing the horizontal distribution of equivalent potential temperatures in Kyusyu during the period from 20th of June to 10th of September, 1939, was made. The authors then investigated the relations between the occurrence of heat thunderstorms and the surface distribution of equivalent potential temperatures, expecting that high equivalent potential temperatures are responsible for thundery conditions.
Unexpectedly, however, heat thunderstorms did not necessarily originate over the regions where the equivalent potential temperatures were high. The adopted method of determining the thundery conditions was to get the critical values of equipotential temperature at which a thunderstorm has not cccurred, though these values varied at each station. After statistical studies, more than 80% of all the thunderstorms occurred when the equivalent potential temperatures at stations near the origin were higher than the critical values.

著者関連情報
© 社団法人 日本気象学会
前の記事 次の記事
feedback
Top