21 業務用建物に導入された太陽熱給湯システムの長期性能分析と改善案検討
*深田 彩心, 吉永 美香
著者情報
会議録・要旨集 フリー

p. 67-70

詳細
抄録

A 6-year operational analysis was conducted on the solar water heating system installed at the convention center. The results showed an average solar fraction of approximately 10%. The recorded solar heat utilization amount was less than half of the estimated collector heat collection, indicating significant heat loss in the collector piping. Furthermore, the storage tank is operating at half its design capacity, which is also considered to be suppressing the thermal collection.