設計工学・システム部門講演会講演論文集
Online ISSN : 2424-3078
セッションID: 3309
会議情報
3309 データセンタ全体の省電力化制御技術 : 第3報 IT・空調連携省電力制御の実証(OS3-2 デジタルエンジニアリングII)
小林 弘樹小林 丈久小林 左千夫橋間 正芳佐藤 裕一
著者情報
会議録・要旨集 フリー

詳細
抄録
Request for power saving of data centers in Japan becomes higher due to the fact that almost all nuclear power plants have been shut down after the Tohoku Earthquake. Target of our research is to establish a control method to save electric power of total datacenter including facilities and ICT instruments. In our first paper on datacenter power saving, we have described an energy simulator which estimates the total electric power of datacenter and evaluates power saving controls of datacenter. In our second paper, we have presented an original real-time thermal fluid simulator and have showed that power consumption of the whole datacenter can be reduced up to 30% and more by workload consolidation and optimal cooling control. In this paper we show that 50% and more power saving is feasible by a coupling control of ICT and cooling facilities for an actual datacenter with 160 servers and an outdoor air cooling system.
著者関連情報
© 2012 一般社団法人 日本機械学会