環境工学総合シンポジウム講演論文集
Online ISSN : 2424-2969
会議情報
219 廃棄物処理システムにおける防災対策について : 混合燃料に対する着火抑制効果
永田 勝也納富 信飯野 真悟石井 喬金井 郁恭板谷 真積
著者情報
会議録・要旨集 フリー

p. 217-220

詳細
抄録
Gasification melting system is necessary for recycling and volume reduction of solid waste. however, many explosions accidents are caused by combustible gases filled in shredding or gasification melting process from gas cylinder and spray-can mixed within bulky waste. In this experiment, inhibition of ignition of mixed fuel composed of C_3H_8,CO and H_2,N_2 or CO_2 as the inert gas is analyzed using a spark plug as the source of ignition. As a result, 1) in waste grinder a lot of attention is needed for DME, because the ignition area of DME is larger than that of C_3H_8 and CH_4,2) according to the ignition limit calculated by Le Chatelier's formula, the security is ascertained at Pyrolysis Furnace, 3) the ignition limit is valued by the pace of increase of temperature and the product of organic radical and O containning radical.
著者関連情報
© 2002 一般社団法人 日本機械学会
前の記事 次の記事
feedback
Top