環境工学総合シンポジウム講演論文集
Online ISSN : 2424-2969
会議情報
447 吸収冷凍機の最適設計に関する検討 : 第 2 報 : 二重効用吸収サイクルへの適用
秋間 雄二梶谷 俊朗鄭 宗秀齋藤 潔河合 素直
著者情報
会議録・要旨集 フリー

p. 537-540

詳細
抄録
Despite the fact that an absorption refrigerator is required to improve its efficiency, even the optimum design point of the absorption cycle has not been clarified. This research discusses the optimum design method of a double-effect absorption refrigerator, which has spread generally. The objects of the analysis are the three typical double-effect absorption cycles, series, reverse and parallel flow. COP is the evaluation function. Some constraints to drive the absorption cycle normally exist. As the analysis technique, the exterior-point-penalty-function method, which can analyze nonlinear optimization problems with constraints, and the applying-trial-and-error method are adopted to seek the optimum point. As a result, optimum COP for each flow at the point of 90% temperature efficiency were, series 1.47,Reverse 1.49 and parallel. 50.
著者関連情報
© 2002 一般社団法人 日本機械学会