Abstract
In previous report, the absorption cycle without an electric solution pump was proposed. To realize this cycle the porous material was embedded in the generator to keep the pressure difference between high pressure for a condenser and low pressure for an absorber. And the tube-type generator was tested to keep the pressure difference for refrigeration. In result the pressure difference was kept using capillary pumping, but the capillary pumping to the circumference direction reduced the heat flux to the generator. In this study to accomplish higher heat flux to the generator, plate-type generator was manufactured and underwent some experiments changing the heat flux to the generator and cooling water temperature.