403 Study on Outside Air Economizer Systems for Data Centers
Yosuke UDAGAWAMasahide YANAGIShisei WARAGAI
Author information
CONFERENCE PROCEEDINGS FREE ACCESS

Details
Abstract
A outside air economizer systems is one effective solution for reducing the power consumption of air conditioning systems. In recent years, outside air economizer systems have gained the spotlight in Japan, so we have conducted a survey and simulation-based estimation toward their introduction. The estimation results have shown that the water-side economizer requires doubling the capacity of the cooling tower and consideration of the installation space and cost, while the air-side economizer increases the humidifying power, which requires the relaxation of indoor humidity specifications. According to this simulation-based comparison results, the package-type air-conditioning unit with an expanded scope of low pressure ratio control has the lowest power consumption per year.