環境工学総合シンポジウム講演論文集
Online ISSN : 2424-2969
セッションID: 430
会議情報

相領域変化を考慮した熱交換器の性能シミュレーション
涌井 徹也, *沖山 大晃, 横山 良平
著者情報
会議録・要旨集 フリー

詳細
抄録

A numerical simulation model of a plate-fin and tube type heat exchanger, which can switch a three phase state model with superheat, saturation, and subcool states and a two phase model with superheat and saturation states in accordance with operational conditions, is developed. Three and two phase models consist of mass, momentum, and energy balance equations for working fluid and air and result in a set of nonlinear algebraic equations, which is solved using a Newton-Raphson method. The switching from a three phase model to a two phase model is conducted when the heat transfer tube length in the subcool region becomes shorter than a threshold value. The switching from a two phase model to three phase model is conducted when the specific enthalpy of working fluid at the outlet of the heat exchanger is smaller than that of saturated liquid. A steady-state performance analysis on an air-cooled condenser, employed in a vapor compression heat pump system, reveals effectiveness of the developed switching approach for the consideration of the phase region change.

著者関連情報
© 2017 一般社団法人 日本機械学会
前の記事 次の記事
feedback
Top