ソース・レセプター関係を用いた空調機群の最適制御手法の逆推定
*松尾 智仁鹿山 和真嶋寺 光近藤 明
著者情報
会議録・要旨集 認証あり

詳細
抄録

In order to provide a comfort thermal environment to each occupant whose clothing and thermal sensitivity are different, it is necessary to make a proper temperature gradient in a room. In this study, an inverse method using source-receptor (SR) relationship was used to estimate optimal inlet temperature of each air conditioner to make temperature field close to objective field. To validate the method, the method was applied on an existing class room. The SR relationship was calculated by CFD simulation, and the optimal inlet temperature to approximate temperature field to objective field was estimated by using SR relationship. Though the method worked well, the improvement was small in the numerical experiment, because of spatially weak relationship between the inlet temperature and indoor temperature field.